KYN28A-□ Removable AC Metal-clad Switchgear

The KYN28A Removable AC Metal-clad Switchgear (hereinafter referred to as"switchgear")is suitable for three-phase AC 50Hz power system.It is used for receiving and distributing electrical energy and controling.protecing,and monitoring cicuits.The newly introduced high-curent,high-breaking switchgear can also be used independently for high-voltage generator outlets.

Keywords:

KYN28A-□ Removable AC Metal-clad Switchgear

Product Description

  • 产品描述
  • The KYN28A Removable AC Metal-clad Switchgear (hereinafter referred to as"switchgear")is suitable for three-phase AC 50Hz power system.It is used for receiving and distributing electrical energy and controling.protecing,and monitoring cicuits.The newly introduced high-curent,high-breaking switchgear can also be used independently for high-voltage generator outlets.

    This product conforms to the standards: GB3906 "3.6 ~ 40.5 kV AC metal enclosed switchgear", GB11022 "Common technical requirements of standards for high-voltage switchgear and control equipment" and IEC298 "AC metal enclosed switchgear and control equipment with rated voltage above 1kV and below 50kV".

    Technical   parameters  :

    Item Unit Parameters
    Rated Voltage kV 3.6、7.2、12、24
    Rated Frequency Hz 50
    Crcuit Breaker Rated Curent A 630、1250、1600、2000、2500、3150
    Switchgear Rated Current A 630、1250、1600、2000、2500、3150
    Rated Short-Time Withstand Curent(4s) kA 16、20、25、31.5、40、50
    Rated Peak Withstand Curent (Peak) kA 40、50、63、80、100、125
    Rated Short-Circuit Breaking Curent kA 16、20、25、31.5、40、50
    Rated Short-Circuit Making Current (Peak) kA 40、50、63、80、100、125
    Rated Insulation Level Power-Frequency Withstan Voltage For 1 Minute Between poles,poles to the ground kV 24、32、42、65
    Between fractures kV 24、32、48、79
    Lightning Impulse Withstand Voltage(Peak) Between poles,poles to the ground kV 40、60、75、125
    Between fractures kV 46、70、85、145
    Protection grade The shell is IP4X,and when the doors between compartments and circuit breakers are open,it is IP2X

    Note:1.The short-circuit capacity of current transformers should  be considered separately.

    2.Technical parameters for ZN63A can be found in the corresponding sample.

    3.For altitudes of 1000m,rated current should bes1250A,and rated short-circuit breaking current should be≤31.5kA