undefined
+
  • undefined

GCS Low Voltage Withdrawable Switchgear

The GCS type low voltage withdrawable Switchgear (hereinafter refered to as "switchgear’’)is designed and developed by our company to meet thee requirements of design units and power users.It is in line with the national conditions.has high technical performance indicators,is adaptable to the development needs of the power market,and can compete with existing imported products.The product is widely used by power users and is suitable for distribution systems in industries such as power plants,petroleum,chemical,metallurgy,textiles,and high-rise buildings.

Keywords:

GCS Low Voltage Withdrawable Switchgear

Product Description

  • 产品描述
  • The GCS type low voltage withdrawable Switchgear (hereinafter refered to as "switchgear’’)is designed and developed by our company to meet thee requirements of design units and power users.It is in line with the national conditions.has high technical performance indicators,is adaptable to the development needs of the power market,and can compete with existing imported products.The product is widely used by power users and is suitable for distribution systems in industries such as power plants,petroleum,chemical,metallurgy,textiles,and high-rise buildings.

    It is used in low-voltage complete distribution devices for power generation,distribution,centalized control of motors,and reactive power compensation in systems with a rated frequency of 50(60)Hz,a rated working voltage of 380V(400V),(660V),and a rated current of 6300A and below.

    This product complies with the standards GB7251 Low-voltage Switchgear and control equipment;"JB/T9661 Low-voltage withdrawable switchgear: IEC61439-1"Low-voltage Switchgear and control equipment."

    Technical parameters:

    Main circuit rated voltage(V) AC380(400),(660)
    (VAuxiliary cicuit rated voltage(V) AC220,380(400),DC 110,220
    Rated frequency (H2) 50(60)
    Rated insulation voltage(V) 660(1000)
    Rated curent (A) Horizontal busbar ≤4000
    (MCCVertical busbar (Mcc) 1000
    Busbar rated short-time withstand current(k/vi s) 50,80
    Busbar rated peak withstand current(kN0.1s) 105,176

    Power frequency test voltage

     (V/1min)
    Main circuit 2500
    Auxiliary cicuit 1760
    Busbar Three-phase four-wire system A,B.C,PEN
    Three-phase five-wire system A,B.C,PEN
    Protection level IP30,IP40

    Main  Circuit  Schemes

    The switchgears main circuit has a total of 32 sets and 118 specifications(refer to Table 2).This includes schemes and specifications derived from changes in the auxilary circuit's control and protection.It caters to the needs of power generation,supply,and other power users,with a rated working curent of 4000A.It is suitable for distribution transformers of 2500kVA and below.

    Additionally,capacitor compensation cabinets are designed to met the demand for improving power factorsin power supply and usage.Reactor cabinets are designed considering comprehensive investment needs.

Product Inquiry