undefined
+
  • undefined

S13, S20, S22 10kV oil immersed transformers

S13, S20 and S22 are energy-saving products. Our company independently developed these products by relying on the research

Category:

Keywords:

S13, S20, S22 10kV oil immersed transformers

Product Description

  • 产品描述
  • S13, S20 and S22 are energy-saving products. Our company independently developed these products by relying on the research and application of new materials and new processes, adopting a model that combines independent innovation with technology introduction, and conduction optimized and innovative design of the core and coil structure to achieve the goal of reducing no-load loss and noise. 

    S13-M-(50~2500)/10 Three-phase oil-immersed distribution transformer
    Rated
    capacity
    (kVA)
    Voltage Combination Connection
    symbol
    No-load loss
    (W)
    Load loss
    (75℃)(W)
    No-load
    current(%)
    Impedance
    voltage(%)
    High voltage
    (kV)
    Tapping range
    (%)
    Low voltage
    (kV)
    50 6
    6.3
    10
    10.5
    11
    ±2×2.5
    ±5
    0.4 Dyn11
    Yyn0
    100 910/870 1.2 4.0
    100 150 1580/1500 0.9
    200 240 2730/2600 0.8
    250 290 3200/3050 0.7
    315 340 3830/3650 0.7
    400 410 4520/4300 0.6
    500 480 5410/5150 0.6
    630 570 6200 0.5 4.5
    800 700 7500 0.5
    1000 830 10300 0.5
    1250 970 12000 0.40
    1600 1170 14500 0.40
    2000 1360 18300 0.3 5.0
    2500 1600 21200 0.3

    Note: For transformers with a rated capacity of 500 kVA and below, the load loss values above the diagonal line in the table apply to the Dyn1l connection group, while those below the diagonal line apply to the Yyn0 connection group.

    S13-M-(50~2500)/10 Three-phase oil-immersed distribution transformer
    Rated
    capacity
    (kVA)
    Voltage Combination Connection
    symbol
    No-load loss
    (W)
    Load loss
    (75℃)(W)
    No-load
    current(%)
    Impedance
    voltage(%)
    High voltage
    (kV)
    Tapping range
    (%)
    Low voltage
    (kV)
    50 6
    6.3
    10
    10.5
    11
    ±2×2.5
    ±5
    0.4 Dyn11
    Yyn0
    100 910/870 1.2 4.0
    100 150 1580/1500 0.9
    200 240 2730/2600 0.8
    250 290 3200/3050 0.7
    315 340 3830/3650 0.7
    400 410 4520/4300 0.6
    500 480 5410/5150 0.6
    630 570 6200 0.5 4.5
    800 700 7500 0.5
    1000 830 10300 0.5
    1250 970 12000 0.40
    1600 1170 14500 0.40
    2000 1360 18300 0.3 5.0
    2500 1600 21200 0.3

    Note: For transformers with a rated capacity of 500 kVA and below, the load loss values above the diagonal line in the table apply to the Dyn1l connection group, while those below the diagonal line apply to the Yyn0 connection group.

    S22-M-(50~2500)/10 Three-phase oil-immersed distribution transformer
    Rated
    capacity
    (kVA)
    Voltage Combination Connection
    symbol
    No-load loss
    (W)
    Load loss
    (75℃)(W)
    No-load
    current(%)
    Impedance
    voltage(%)
    High voltage
    (kV)
    Tapping range
    (%)
    Low voltage
    (kV)
    50 6
    6.3
    10
    10.5
    11
    ±2×2.5
    ±5
    0.4 Dyn11
    Yyn0
    80 655/625 1.2 4.0
    100 120 1140/1080 0.9
    200 190 1970/1870 0.8
    250 230 2300/2195 0.7
    315 270 2760/2630 0.7
    400 330 3250/3095 0.6
    500 385 3900/3710 0.6
    630 460 4460 0.5 4.5
    800 560 5400 0.5
    1000 665 7415 0.5
    1250 780 8640 0.40
    1600 940 10440 0.40
    2000 1085 13180 0.3 5.0
    2500 1280 15270 0.3

    Note: For transformers with a rated capacity of 500 kVA and below, the load loss values above the diagonal line in the table apply to the Dyn1l connection group, while those below the diagonal line apply to the Yyn0 connection group.

Product Inquiry

We highly value your feedback and inquiries. If you have any questions about our products or services, please fill out the form below, and we’ll get in touch with you as soon as possible.