SCB13, SCB14, SCB18 10kV dry-type transformers

The product has a wide range of application and is particularly suitable for places with high fire-prevention requirements, such as mines, oil fields, subway, power plants, schools hospitals, Commercial Centers, high-rise buildings and all indoor configuration systems

Category:

Keywords:

SCB13, SCB14, SCB18 10kV dry-type transformers

Product Description

  • 产品描述
  • The product has a wide range of application and is particularly suitable for places with high fire-prevention requirements, such as mines, oil fields, subway, power plants, schools hospitals, Commercial Centers, high-rise buildings and all indoor configuration systems

    Main performance parameters of 10kV SCB13 dry transformer
    ModelRated
    capacity
    (kVA)
    Voltage CombinationConnection
    symbol
    No-load loss
    (W)
    Load loss(W)No-load
    current(%)
    Impedance
    voltage(%)
    High voltage
    (kV)
    Tapping range
    (%)
    Low voltage
    (kV)
    130(B)155(F)180(H)
    (100 ℃)(120 ℃)(145 ℃)
    SCB13-50506
    6.3
    10
    10.5
    11
    ±2.5
    ±5
    0.4Dyn11
    Yyn0
    1958459009652.04.0
    SCB13-1001002901330141015201.5
    SCB13-200200±2×2.5
    ±5
    4452130227024401.1
    SCB13-2502505152330248026600.9
    SCB13-3153156352940312033500.8
    SCB13-4004007053370359038500.8
    SCB13-5005008354130439047000.8
    SCB13-6306309355050536057600.706.0
    SCB13-80080010955890626067100.70
    SCB13-1000100012756880731078800.70
    SCB13-1250125015058190872093300.70
    SCB13-160016001765994010500113000.70
    SCB13-2000200021951220013000140000.60
    SCB13-2500250025901450015400166000.60

    Note: The load losses listed in the table represent values for different insulation heat resistance classes at the reference temperatures indicated in parentheses (as specified in GB/T 1094.11). For load losses of other insulation heat resistance classes not included in the table, corresponding conversion calculations should be performed based on their respective reference temperatures, using the data for the “Class 155 (F)” insulation heat resistance class as a reference.

    Main performance parameters of 10kV SCB14 dry transformer
    ModelRated
    capacity
    (kVA)
    Voltage CombinationConnection
    symbol
    No-load loss
    (W)
    Load loss(W)No-load
    current(%)
    Impedance
    voltage(%)
    High voltage
    (kV)
    Tapping range
    (%)
    Low voltage
    (kV)
    130级(B)155(F)180(H)
    (100 ℃)(120 ℃)(145 ℃)
    SCB13-50506
    6.3
    10
    10.5
    11
    ±2.5
    ±5
    0.4Dyn11
    Yyn0
    1858459009652.04.0
    SCB13-1001002701330141015201.5
    SCB13-200200±2×2.5
    ±5
    4202130227024401.1
    SCB13-2502504902330248026600.9
    SCB13-3153156002940312033500.8
    SCB13-4004006653370359038500.8
    SCB13-5005007904130439047000.8
    SCB13-6306308855050536057600.706.0
    SCB13-80080010355890626067100.70
    SCB13-1000100012056880731078800.70
    SCB13-1250125014208190872093300.70
    SCB13-160016001665994010500113000.70
    SCB13-2000200020751220013000140000.60
    SCB13-2500250024501450015400166000.60

    Note: The load losses listed in the table represent values for different insulation heat resistance classes at the reference temperatures indicated in parentheses (as specified in GB/T 1094.11). Load losses for other insulation heat resistance classes not included in the table should be calculated by scaling the data for the “Class 155 (F)” insulation heat resistance class according to their respective reference temperatures.

    Main performance parameters of 10kV SCB14 dry transformer
    ModelRated
    capacity
    (kVA)
    Voltage CombinationConnection
    symbol
    No-load loss
    (W)
    Load loss(W)No-load
    current(%)
    Impedance
    voltage(%)
    High voltage
    (kV)
    Tapping range
    (%)
    Low voltage
    (kV)
    130(B)155(F)180(H)
    (100 ℃)(120 ℃)(145 ℃)
    SCB13-50506
    6.3
    10
    10.5
    11
    ±2.5
    ±5
    0.4Dyn11
    Yyn0
    1558459009652.04.0
    SCB13-1001002301330141015201.5
    SCB13-200200±2×2.5
    ±5
    3602130227024401.1
    SCB13-2502504152330248026600.9
    SCB13-3153155102940312033500.8
    SCB13-4004005703370359038500.8
    SCB13-5005006704130439047000.8
    SCB13-6306307505050536057600.706.0
    SCB13-8008008755890626067100.70
    SCB13-1000100010206880731078800.70
    SCB13-1250125012058190872093300.70
    SCB13-160016001415994010500113000.70
    SCB13-2000200017601220013000140000.60
    SCB13-2500250020801450015400166000.60

    Note: The load losses listed in the table correspond to different insulation heat resistance classes at the reference temperatures indicated in parentheses (as specified in GB/T 1094.11). For load losses of other insulation heat resistance classes not included in the table, calculate the corresponding values based on their respective reference temperatures using the data for the “Class 155 (F)” insulation heat resistance class as a reference.

    Dry Type Transformer is a safe and efficient power distribution solution designed for commercial, industrial, and infrastructure applications. Featuring low losses, excellent insulation, and reliable performance, it operates without oil, reducing fire risks and maintenance requirements. Suitable for buildings, factories, hospitals, data centers, and renewable energy projects, the transformer offers stable power transmission, environmental friendliness, and long service life. Custom specifications are available to meet diverse electrical system requirements.